Concealed Fan Coil

 

C fan coil 2

Features:

 

·Three speed quiet running fan

·Heavy duty zinc-coated, erosion resistant steel construction

·Horizontal concealed installation

 

 

 

Concealed Fan Coil typical installation

 

Concealed Fan Coil

 

Concealed Fan Coil Technical data

 

Index
Item
FP-34 
FP-51
FP-68
FP-85
FP-102
FP-136
FP-170
FP-204
FP-238
Nominal Air Flow
H
M3/h
380
550
710
850
1050
1450
1700
2100
2500
M
M3/h
300
440
570
680
840
1160
1360
1680
2000
L
M3/h
230
330
430
510
630
870
1020
1260
1500
Cooling Capacity
H
W
2150
2990
4150
5040
5930
7880
9100
10800
12950
M
W
1910
2700
3730
4400
5250
7080
8170
9700
11620
L
W
1660
2310
3150
3700
4410
6100
6990
8360
9980
Heating Capacity
H
W
3220
4403
5949
7265
8357
11685
13270
16065
18000
M
W
2840
3787
5176
6321
7187
10166
11545
13977
15000
L
W
2390
3214
4402
5376
6101
8647
9821
11727
13000
Power Input
H
W
46
48
53
64
78
110
130
165
200
M
W
36
37
42
45
63
80
98
135
165
L
W
25
28
32
36
47
64
76
128
138
Noise
H
dB(A)
35
36
38
40
42
43
45
47
49
M
dB(A)
30
31
33
35
38
38
40
42
45
L
dB(A)
24
25
27
29
32
32
34
36
39
Coil
Type
Copper coil + Aluminum Fin
Working Pressure
1.6 Mpa
Water qty. (kg/h)
396
570
720
867
1140
1350
1570
1860
2230
Pressure Drop (kpa)
10
20
25
35
45
30
42
50
60
Fan
Type
Two air inlet centrifugal
Quantity
1
1
2
2
2
3
4
4
4
Motor
Type
Three speed,single phase
Quantity
1
1
1
1
1
2
2
2
2
Connection
Inlet / Outlet
3/4〞 Tape pipe female thread
Condensing Water
3/4〞 Tape pipe male thread
Electric
Five Termianl: H/M/L/N/G
N.W.
Horizontal Concealed
15
17
25
28
29
33
42
44
45
HC with air return box
17
19
29
32
34
38
48
52
53
Vertical concealed
20
21
25
29
32
42
50
54
56
Vertical exposed
23
24
28
32
35
45
53
57
59
Horizontal exposed
20
21
25
29
32
42
50
53
54
 Remark:
 1.This cooling performance is based on: inlet water temp. 7℃,outlet water temp.12℃ and air  
 temp.DB27℃,WB19.5℃ .
 2.This heating performance is based on: inlet water temp. 60℃,outlet temp.55℃ and air temp.DB21℃.
 3.This noise is tested at position 1M distance from the front and bottom side of the unit.

 

No data for now